Description: Provided an IAQ assessment of an office located in a municipal parking garage. The assessment included air constituent, air contaminant, and biologics monitoring. The office was serviced by a central HVAC unit for the parking garage. All air contaminants were within recommended EPA/OSHA/NIOSH limits. Carbon dioxide levels were up to four times outside levels. In addition, bacterial and fungal contaminations were found in AC drip pans where water had collected and no regular maintenance was conducted. Recommendations included a maintenance schedule for HVAC returns and exhausts, the addition of a separate or upgraded HVAC system, the use of alternate air dampers to increase occupant comfort levels, the implementation of a regular maintenance schedule for room AC units including the addition of biocide, and reporting of testing results to the building occupants. An additional recommendation made was to complete diagrams of the HVAC system in the building since vents were found that were not hooked to the system in any way.
 