Project Name: Facility IAQ
Country: USA
Description: Provided an IAQ assessment of the office areas of a textile industrial facility. The survey included air constituent and air contaminant monitoring. Also, inspections of the HVAC systems were conducted to identify any buildup from dust, mold, or mildew and to identify possible malfunctions in the systems. The survey concluded that no air constituents or air contaminants were outside recommended EPA/OSHA/NIOSH limits. Several rooms were found to have borderline carbon dioxide levels (800 ppm) even during low occupancy levels. Recommendations included a full maintenance check of HVAC systems including returns and exhausts, balancing of temperature between rooms sharing an HVAC system, the increase in fresh air intake for all systems and reporting of testing results to the building occupants.
 