Projects

Project Details

Project Name: Provided an IAQ Assessment
Country: USA
Description: Provided an IAQ assessment of an isolated office located next to a parking garage. The assessment included air constituent and air contaminant monitoring. The office was not serviced by an HVAC system, but a small window air conditioner was used for ventilation. All air contaminants were within recommended EPA/OSHA/NIOSH limits. However, carbon monoxide was detected at low levels in the garage area next to the office. Carbon dioxide levels were up to six times outside levels. The maximum level measured was 1800 ppm. The major recommendation was to add this office to a ventilation source so that increased air flow could be added. A follow-up assessment was completed after maintenance procedures had been carried out and a new ventilation system had been added. The carbon dioxide levels had been cut by more than four times in the office area.
 